Skip to main content

SDR-120-24 AC-DC Industrial DIN rail power supply; Output 24Vdc at 5A

610.3 KB
Loading PDF...
of --
100%

SDR-120-24 AC-DC Industrial DIN rail power supply; Output 24Vdc at 5A; Metal casing; Ultra slim width 40mm

Document Text

Show document text (626 words)

120W Single Output Industrial DIN RAIL with PFC Function SDR-120 series ■ User’s Manual ‧ ‧ ‧ ‧  ‧ ‧ ‧ ‧BS EN/BS EN/ ‧ ‧ ■  ‧   Bauar t gepruft Sicherheit SE PQ egel ma ge od o s M be wac g IF 47 www.tuv.com ID 2000000000

SPECIFICATION AS/NZS62368-1 TPTC004 UL508 BS EN/EN62368-1 IEC62368-1

MODEL SDR-120-12 SDR-120-24 SDR-120-48 DC VOLTAGE 12V 24V 48V RATED CURRENT 10A 5A 2.5A CURRENT RANGE 0 ~ 10A 0 ~ 5A 0 ~ 2.5A RATED POWER 120W 120W 120W PEAK CURRENT 15A 7.5A 3.75A PEAK POWER Note.6 180W (3 sec.) OUTPUT RIPPLE & NOISE (max.) Note.2 100mVp-p 100mVp-p 120mVp-p VOLTAGE ADJ. RANGE 12 ~ 14V 24 ~ 28V 48 ~ 55V VOLTAGE TOLERANCE Note.3 ±1.0% ±1.0% ±1.0% LINE REGULATION ±0.5% ±0.5% ±0.5% LOAD REGULATION ±1.0% ±1.0% ±1.0% SETUP, RISE TIME 1500ms, 60ms/230VAC 3000ms, 60ms/115VAC at full load HOLD UP TIME (Typ.) 20ms/230VAC 20ms/115VAC at full load VOLTAGE RANGE Note.7 88 ~ 264VAC 124 ~ 370VDC FREQUENCY RANGE 47 ~ 63Hz POWER FACTOR (Typ.) 0.93/230VAC 0.96/115VAC at full load INPUT EFFICIENCY (Typ.) 89% 91% 90.5% AC CURRENT (Typ.) 1.4A/115VAC 0.7A/230VAC INRUSH CURRENT (Typ.) 35A/115VAC 70A/230VAC LEAKAGE CURRENT <1mA / 240VAC Normally works within 110 ~ 150% rated output power for more than 3 seconds and then shut down o/p voltage OVERLOAD >150% rated power, constant current limiting with auto-recovery within 3 seconds and shut down o/p voltage after 3 seconds 14 ~ 17V 29 ~ 33V 56 ~ 65V PROTECTION OVER VOLTAGE Protection type : Shut down o/p voltage, re-power on to recover 95℃±5℃ (TSW) detect on heatsink of power switch OVER TEMPERATURE Protection type : Shut down o/p voltage, recovers automatically after temperature goes down FUNCTION DC OK REALY CONTACT RATINGS (max.) 60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load WORKING TEMP. -25 ~ +70℃ (Refer to "Derating Curve") WORKING HUMIDITY 20 ~ 95% RH non-condensing ENVIRONMENT STORAGE TEMP., HUMIDITY -40 ~ +85℃, 10 ~ 95% RH TEMP. COEFFICIENT ±0.03%/℃ (0 ~ 50℃) VIBRATION Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 SAFETY STANDARDS UL508, TUV BS EN/EN62368-1, AS/NZS 62368.1, EAC TP TC 004,BSMI CNS14336-1 approved;(meet BS EN/EN60204-1) WITHSTAND VOLTAGE I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC SAFETY & ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH EMC EMC EMISSION Compliance to BS EN/EN55032 (CISPR32), BS EN/EN61204-3 Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020, CNS13438 Class B (Note 4) Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55024, BS EN/EN61000-6-2 (BS EN/EN50082-2), EMC IMMUNITY BS EN/EN61204-3, heavy industry level, EAC TP TC 020, SEMI F47 approved MTBF 1764.6K hrs min. Telcordia SR-332 (Bellcore) ; 292.1K hrs min. MIL-HDBK-217F (25℃) OTHERS DIMENSION 40*125.2*113.5mm (W*H*D) PACKING 0.67Kg; 20pcs/14.4Kg/1.16CUFT NOTE ℃         ℃℃ ※:https://www.meanwell.com/serviceDisclaimer.aspx File Name:SDR-120-SPEC 2022-02-28

120W Single Output Industrial DIN RAIL with PFC Function SDR-120 series Mechanical Specification Case No.992A Unit:mm

113.5 125.2 TB2 TB1

DC OK 1

+V ADJ. 1

DC OK 2 40

2 3 4 3

+

Terminal Pin No. Assignment (TB1) Pin No. Assignment 1 FG 2 AC/N 3 AC/L 35

Terminal Pin No. Assignment (TB2) Pin No. Assignment ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15 1,2 Relay Contact 3 DC OUTPUT -V 4 DC OUTPUT+V

Block Diagram

DC OK

EMI FILTER PFC POWER RECTIFIERS +V I/P & SWITCHING & CIRCUIT -V RECTIFIERS FILTER O.C.P. U.V.P. O.L.P. FG DETECTION PWM & PFC CIRCUIT PFC CONTROL CONTROL O.V.P.

DC OK Relay Contact

Contact Close PSU turns on / DC OK. Contact Open PSU turns off / DC Fail. Contact Ratings (max.) 30V/1A resistive load.

File Name:SDR-120-SPEC 2022-02-28

120W Single Output Industrial DIN RAIL with PFC Function SDR-120 series Peak Loading (1) (2)

180W 180W

120W 60W 100 sec. 3 sec. 15 sec. 3 sec.

Derating Curve Output derating VS input voltage

Others 100 150 90 125 For 3 sec. (typ.) 12V 80 Others 100 70 LOAD (%)

LOAD (%)

60 75 Continuous 12V 50 60 40

-25 0 10 20 30 40 50 55 60 70 (VERTICAL) 88 100 110 135 155 230 264

AMBIENT TEMPERATURE (℃) INPUT VOLTAGE (V) 60Hz

File Name:SDR-120-SPEC 2022-02-28

Documentation Type